Samlexpower SEC-60BRM-220 Specifications

Browse online or download Specifications for Power supply units Samlexpower SEC-60BRM-220. Samlexpower SEC-60BRM-220 Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
MODELS : SEC-40BRM-220
SEC-60BRM-220
SEC-80BRM-220
SEC-100BRM-220
Please read this manual before operating your power supply.
INSTALLATION & OPERATING MANUAL
EXPANDABLE DC POWER SUPPLY
230V AC INPUT
N+1 DC Power System
with Battery Backup / Charging Function
Page view 0
1 2 3 4 5 6 ... 23 24

Summary of Contents

Page 1 - N+1 DC Power System

MODELS : SEC-40BRM-220 SEC-60BRM-220 SEC-80BRM-220 SEC-100BRM-220 Please read this manual before operating your power supply.

Page 2

7. Regulated output voltage of 14.2VDC +/ - 1% from the modules ( measured at screw terminals S5 and S6 (Fig.1) is fed to the positive and negative DC

Page 3 - TABLE OF CONTENTS

8. If the input A.C. power is interrupted, the external battery feeds the load instantane-ously through the Schottky Diode D2 (D2 will by-pass the res

Page 4 - CAUTION !

9. The output voltage of the paralleled modules or the common DC bus (before the Schottky Di-odes D1) can be adjusted between 13.8 V and 14.6 V by adj

Page 5

10. UPGRADING TO HIGHER CAPACITY – INSTALLING ADDITIONAL MODULE(S) Additional optional module(s) (Model No. SEC-2012MPSB-220) can be added to upgrade

Page 6 - 1. N+1 redundant systems

REMOVING A DEFECTIVE MODULE 1. Remove the top cover plate by unscrewing the 10 screws. 2. Locate the defective module. Remove the 6 screws from

Page 7

“ PSM STATUS ” LED(S) DOES NOT LIGHT UP · The associated module has become defective. The unit will still operate normally as the remaining working

Page 8

LIMITING ELECTROMAGNETIC INTERFERENCE (EMI) 1. Switched mode power supplies ( SMPS ) employ high frequency switching and thus, are a source of radi

Page 9

5. The conducted RF noise from these power supplies is limited to the maximum allowable levels by internal filtration. The filtered RF noise currents

Page 10 - FUGURE A

c. Twist the positive and negative wires from the output of the power supply to the radio d. The DC side positive and negative outputs of these po

Page 11

SPECIFICATIONS NO. OF MODULES 2 3 4 5 INPUT VOLTAGE RANGE 210 TO 250 V AC, 50/60 HZ INPUT CURRENT 4A 6A 8

Page 12

• PROVIDES N + 1 REDUNDANCY • ALLOWS CONNECTION OF EXTERNAL BATTERIES FOR BACKUP • EXPAND OUTPUT POWER BY ADDING POWER MODULES • UP TO 100 AMPS CO

Page 13

Figure 1 - Layout of Power Supply Module S1 to S4 Holes for 4 screws to fasten the module to the chassis S5 & S6 Holes for 2 scre

Page 14

CONTINUITY OF “ DAISY CHAIN “ CONNECTIONS Removing any end module (example PSM1/PSM5 in Fig. 2 above) does not break the daisy chain. However, if an

Page 15

2 YEAR Limited Warranty This product manufactured by Samlex America, Inc. (the “Warrantor”) is warranted to be free from defects in workmanship and

Page 16

Attach copy of receipt here for your records: Date purchased: Additional notes: Purchased from: 20.

Page 17

Thank you for purchasing a Samlex power supply product ! Samlex America Inc. 110 –17 Fawcett Road Coquitlam

Page 18

TABLE OF CONTENTS Topic Page Important safety instructions 1,2 Description and application 3 Desig

Page 19 - SPECIFICATIONS

IMPORTANT SAFETY INSTRUCTIONS Please read before using your power supply. CAUTION ! ALL ELECTRICAL INSTALLATIONS MUST MEET LOCAL AND NA-TIONAL WIR

Page 20

LOAD AND BATTERY CONNECTIONS THE LOAD & BATTERY TERMINALS ON THE POWER SUPPLY HAVE A TUBU-LAR HOLE OF DIAMETER 8mm (0.31”) WITH A SET SCREW. ALW

Page 21

DESCRIPTION This is a 19 inch, 2U height (3.5”) Rack Mount Power Supply which converts 230 V , 50/60 Hz. AC power into regulated 14.2 V DC , +/- 1% (

Page 22 - 2 YEAR Limited Warranty

A warning circuit monitors the operational condition of the fans. In case of a fan failure, a buzzer will sound and the red LED indicating “FAN FAILU

Page 23

REMOTE MONITORING AND SIGNALLING A provision has been made for remote signaling and monitoring of the following operational conditions and parameters

Page 24 - 110 –17 Fawcett Road

FAN FAILURE WARNING INDICATOR AND ALARM: If forced air cooling is stopped due to failure of any one or both the fans, the red “FAN FAILURE“ LED will

Comments to this Manuals

No comments